SUT-100

Flame Scanner

A flame scanner detects the existence of a flame inside the combustion chamber, and aims at preventing fuel injection into the combustion chamber in the absence of flame formation. If the flame goes out, the system protection will operate in one second and issue the fuel valve closing command. This action prevents from fuel accumulation in the combustion chamber and possible explosion.

SUT-100 Flame Scanner

UV Flame Scanner

Sensor

Stainless steel 316

Housing

Quartz glass

Window

3/4´´ internal NPT

Mounting

Lead colors: YellowGreen (Body)

                         Brown (+)

                         Blue (-)

Cable characteristics

5m or 10m

Lead length

-40°C to +100°C (For UV Sensor type 1)

Working Temperature

(Without Cooling)

-40°C to +150°C (For UV Sensor type 2)

IP67

Int. Protection Marking

185-260nm

Average Spectral Sensitivity
Pulse 100sec-1 ± 25sec-1

Output

< 10min-1

Background

< 200ms

Response Time

325VDC ± 25VDC (For UV Sensor type 1)

Power Requirement

500VDC ± 50VDC (For UV Sensor type 2)

 

 

 

اسکنر شعله SUT-100

 

SUT-100 Amplifier

20 … 25VDC

Input Voltage

30 mA (when flame is not detected)

50 mA (While flame is detected)

Input Current

325VDC (For UV Sensor type 1)

Output Voltage

500VDC (For UV Sensor type 2)

Maximum 0.5mA

Output Current

-20°C to +70°C

Working Temperature

Pin1: Flame Relay N.O. (or Open Collector with 3.3kW pulled up resistor)

Connector Description

Pin2 & Pin3 : Flame Relay COM (or GND)

Pin4: Flame Relay N.C.

Pin5 & Pin6 : +24V

Pin7 & Pin8 : GND

Pin9 & Pin10 & Pin 11 & Pin12 : Earth

Pin13 & Pin14 : Anode (+)

Pin15 & Pin16 : Cathode (-)

 

Flame Scanner Ordering Table

Feature

Part Number

SUT-100 Flame Scanner with UV sensor type 1

SUT-100-S18CX7

SUT-100 Flame Scanner with UV sensor type 2

SUT-100-S41CX7


Flame Scanner Amplifier
Ordering Table

Feature

Part Number

SUT-100 Amplifier for UV sensor type 1

SUT-100-A8D124

SUT-100 Amplifier for UV sensor type 2

SUT-100-A7D124

 