fiber optic cable

Features

  • High temperature resistance
  • High vibration tolerance
  • Low space occupation
  • Adjustable to many different mounting positions
  • Suitable for zone 1&2
  • Flexible route from mounting connection to sensor box

Applications

  • Power stations
  • Chemical industry
  • Refineries
  • Cement plants
  • Waste incinerators
  • Steam generators
  • Heating plants
0/5 (0 نظر)
در حال بارگذاری...

Functional description

When all solutions for mounting a sensor on the side glass of a combustion chamber go to fail, there is another solution for scanning the flame by the “Fiber Optic Cable”. Minimum space occupation and high temperature resistance side by very high vibration tolerance are the most important advantages of the fiber optic cable, in this application.

Fiber Optic Cable ordering table

 Description  Fiber optic & head screw code
Optical fiber type 1 – head screw type 1 – UV lens  401
Optical fiber type 1 – head screw type 1 – IR lens  402
Optical fiber type 1 – head screw type 2 – UV lens  411
Optical fiber type 1 – head screw type 2 – IR lens  412
Optical fiber type 2 – head screw type 1 – UV lens  301
Optical fiber type 2 – head screw type 1 – IR lens  302
Optical fiber type 2 – head screw type 2 – UV lens  311
Optical fiber type 2 – head screw type 2 – IR lens  312
Special order on the request  TXX

The “Fiber Optic Cable” can be used in the length from a fraction of a meter to ten meters and the suitable number of elements. Both ends of “Fiber Optic Cable” can be joined to any mechanical connection, by varied head screw types. Also, for different light spectrum of flames, there is two type of lens to apply. There is a specification table of standard optical fiber as below:

Optimal fiber specification

Florine doped silica

Inner-cladding material

Silica

Core material

-40 ~ +300 oC

Operation temperature range

Polyimide

Coating material

200 ± 5 µm

Core diameter

Up to 350 oC

Short term temperature

250 ± 5 µm

Coating diameter

220 ± 5 µm

Cladding diameter

> 22 mm

Long term bend radius

> 17 mm

Short term bend radius

≥ 10 db/km

Attenuation

100 kpsi

Proof test level